OUTDOOR VCB
The EOFVp-36 is the result of consistent further development for application in modern current interruption technology for medium voltage switchgear. It is characterized by compact dimensions. Good operator guidance and a modern functional industrial design. The EOFVp-36 is a porcelain-clad outdoor vacuum circuit breaker supported on steel frames and designed for plinth mounting and is for use on earthed systems. It requires minimum maintenance compared to other circuit breaker technologies and can perform well in harsh conditions. The mechanism of this breaker is designed for the operation of very a short stroke required in vacuum interrupter.
- Three pole operation system
- Robust vacuum interrupters
- Operating mechanism motor driven
- Fully spring-operated mechanism for all range
- Tested to IEC standard
- Simple to install and operate
- Long service life that other types of breaker
- Maintenance reduced at the mInImum
- Operates in all kinds of extreme climate conditions
- Increased safety High mechanical endurance
- Environment friendly in comparison to other types of circuit breaker
OUTDOOR VCB
** This is only exemplary; specifications will vary based on individual client requirements
E0FVp |
TYPE |
||||||||||||||||||
40 |
315 |
26.4 |
3s |
Rated Short time current (STC) |
|||||||||||||||
725 |
725 |
725 |
mm |
Pole center spacing |
|||||||||||||||
36 |
36 |
36 |
kV |
Rated voltage |
|||||||||||||||
70 |
70 |
70 |
kV |
Rated Power frequency withstand voltage |
|||||||||||||||
170 |
170 |
170 |
kV |
Rated lighting impulse withstand voltage |
|||||||||||||||
50 |
50 |
50 |
Hz |
Rated frequency |
|||||||||||||||
2500 |
2000 |
1600 |
1250 |
2500 |
2000 |
1600 |
1250 |
800 |
630 |
2500 |
2000 |
1600 |
1250 |
630 |
A |
Rated (normal) current |
|||
100 |
80 |
66 |
KA |
Rated peak withstand current |
|||||||||||||||
40 |
31.5 |
26.4 |
kA |
Rated short-circuit current |
|||||||||||||||
33 |
33 |
33 |
% |
Percentage value of DC component |
|||||||||||||||
50 |
50 |
50 |
A |
Cable charging breaking current |
|||||||||||||||
. |
. |
. |
0-0.3 s-C0-3 min- C0 |
||||||||||||||||
10000 |
10000 |
10000 |
Drive mechanism |
Mechanical |
Number of operating cycles without overhaul |
||||||||||||||
30000 |
30000 |
30000 |
Interrupter chamber |
||||||||||||||||
10000 |
10000 |
10000 |
Rated (normal) Current |
Electrical |
|||||||||||||||
100 |
100 |
100 |
With rated short-circuit current |
||||||||||||||||
45±10 |
45±10 |
45±10 |
ms |
Opening time |
Breaker operating times |
||||||||||||||
65±10 |
65±10 |
65±10 |
ms |
Closing time |
|||||||||||||||
45-67 |
45-67 |
45-67 |
ms |
Break Time |
|||||||||||||||
07-12. |
07-12. |
07-12. |
ms |
Arc Duration |
|||||||||||||||
20 |
20 |
20 |
ms |
Minimum command time for release coils |
|||||||||||||||
≤20 |
≤20 |
≤20 |
s |
Charging time for the motor drive mechanism |
|||||||||||||||
800 |
750 |
750 |
750 |
750 |
700 |
700 |
700 |
700 |
700 |
650 |
650 |
650 |
650 |
650 |
KG |
Weight (Approximate) |
Send query
Fill out the form and we will get back to you shortly.
INDOOR VACUUM CIRCUIT BREAKER
Energypac remains the first and only company in Bangladesh to introduce horizontal isolated, horizontal draw out type vacuum circuit breaker. The motivation of the top management together with the innovative skills of its R&D team made it possible for this circuit breaker to meet highly demanding needs for performance from all ends including consultants , contractors, industries, and utilities. Large number of circuit breakers are in operation today in Bangladesh and other parts of the world. This 12 kv horizontal isolated, horizontal draw out vacuum circuit breaker type EHHV-12 is highly effective and easy to operate and maintain equipment for distribution at 12W.
- User friendly
- High degree of safety
- High operational reliability
- Rugged design
- Simple in construction
- Modular and compact
- Easy maneuverability
- Extensible with a high degree of customization
INDOOR VACUUM CIRCUIT BREAKER
** This is only exemplary; specifications will vary based on individual client requirements
EHHV-36 |
EHHV-12 |
TYPE |
||
36kv |
12KV |
12KV |
12KV |
kv𝑈rRatedvoltage |
170 |
75 |
28 |
50 |
kv𝑈p Rated lightning impulse withstand voltage |
70 |
75 |
28 |
50 |
kv𝑈d Rated power frequency withstand voltage |
50 |
75 |
28 |
50 |
Hz 𝑓 r Rated frequency |
1250A |
630A |
630A |
630A |
𝐼 k Rated (normal) Current |
80 |
100 |
80 |
62.5 |
KA Hz) (50/60 𝐼 p Rated peak withstand current, equal to rated short circuit making current |
31.5 |
40 |
31.5 |
25 |
KA 3 s tk = 𝐼kRated short-time current |
31.5 |
40 |
31.5 |
25 |
KA 𝐼sc Rated short-circuit breaking current |
33% |
33% |
33% |
33% |
% Percentage value of the DC component |
31.5 KA |
40KA |
31.5kA |
25KA |
|
≤10,000 |
≤10,000 |
≤10,000 |
≤10,000 |
With rated (normal) Current |
≤100 |
≤100 |
≤100 |
≤100 |
With rated short-circuit breaking current |
<50 |
<45 |
<45 |
<45 |
ms Opening time (m an) |
<80 |
<55 |
<55 |
<55 |
ms Closing time (max.) |
15ms |
15ms |
15ms |
15ms |
ms Arc duration (max.) |
<15 |
<12 |
<12 |
<12 |
s Charging time for circuit breaker |
Send query